The Honeywell HE225H8908 is a bypass humidifier designed for whole-home humidity control, typically installed on the warm-air supply (or return) plenum of a forced-air furnace. It works by diverting warm air from the furnace through the humidifier, where water evaporates into the air stream, and then returns the moistened air to the duct system. This manual covers safety, installation, operation, maintenance, and troubleshooting for proper use.
Key components: Bypass humidifier unit, Water panel (evaporative pad), Humidistat control, Bypass duct, Drain hose, Mounting hardware.
| Feature | Description |
|---|---|
| Bypass Design | Uses furnace air flow; no separate fan required |
| Evaporative Pad | Water panel for maximum evaporation and mineral absorption |
| Automatic Humidistat | Wall-mounted or built-in control to set desired humidity level |
| Drain System | Flushes away minerals and impurities from the water panel |
| Bypass Damper | Manual or automatic damper to regulate air flow |
| Mounting Bracket | For secure installation on furnace plenum |
| Water Inlet Valve | Solenoid valve controls water supply to the unit |
| Low Voltage Connection | Connects to furnace transformer (24V) for power |
| Air Flow Direction Arrow | Indicates proper installation orientation |
| Service Light | Indicates when water panel needs replacement |
Unpack and inspect all components. Ensure furnace is off before beginning.
WARNING! Turn off furnace power and water supply before installation. Follow local plumbing and electrical codes.
After installation, restore power and water.
CAUTION! Ensure all connections are tight to prevent leaks. Check for proper drainage within first 24 hours.
Humidistat Control: Mount on wall in living area (not in duct). Settings: OFF, LOW, MEDIUM, HIGH, or numeric scale (0-60% RH).
Operation: Humidistat calls for humidity when indoor RH is below set point, activating furnace blower (or using fan circuit) and opening water valve. Bypass Damper: Manual slide damper to adjust air flow through unit (more open = more humidity). Service Indicator: Light or signal when water panel needs replacement (typically once per season).
Bypass duct connects humidifier to return plenum. Wiring connects to furnace control board or transformer.
Tip: Install humidistat on interior wall away from moisture sources (kitchen, bathroom) for accurate reading.
Set humidistat based on outdoor temperature to prevent window condensation.
WARNING! Excessive humidity can cause condensation and damage. Adjust settings with outdoor temperature changes.
Regular maintenance ensures efficiency and prevents scale buildup.
Turn off power and water before cleaning. Use mild detergent and soft cloth; do not use harsh chemicals.
CAUTION! Do not allow water to contact electrical components. Ensure unit is dry before restoring power.
UL Listed. Complies with applicable standards. Manufactured for residential use. For technical support or warranty service, contact Honeywell Home Customer Care at 1-800-328-5111 or visit www.honeywellhome.com. This product may be covered by one or more U.S. patents.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| No humidity output | Humidistat setting, water supply, furnace blower | Check humidistat is above current RH; ensure water valve open; furnace must be running in heat mode. |
| Water leaking | Loose connections, clogged drain | Tighten fittings; clear drain line; ensure drain hose is not kinked. |
| Mineral buildup on panel | Hard water, old panel | Replace water panel; consider water treatment if severe. |
| Air flow weak | Bypass damper closed, duct blocked | Open bypass damper; check duct for obstructions. |
| Humidistat not calling | Wiring, placement, sensor | Check wiring connections; relocate if near moisture source; test with higher setting. |
| Water not shutting off | Faulty solenoid valve, humidistat | Turn off water supply; check valve for debris; replace if stuck open. |
Reset: Turn humidistat to OFF, then back to desired setting.
Service: 1-800-328-5111; www.honeywellhome.com